Electric multi-turn actuator MOR 3.5PA

Electric multi-turn actuator MOR 3.5PA

Type number: 096
Enclosure: IP 67
Trip torque: 140 to 550 Nm
Rebuild speed: 25 to 40 min−1
Scope of work. of revolutions: 1 to 400
Weight: 65 to 90 kg
Ambient temperature: -60 to 60 °C
Connecting flange: F14, F16
Work position: with the motor axis in a horizontal position (deviation +/-15°)

Hi, my name Is Marko. I will be happy to help/advise you

Ing. Marko Čižmárik

Standard equipment and functions with DMS3 control unit

  • Supply voltage 230 V AC
  • Terminal board connection
  • Thermal protection of the electromotor PTO (switch-off temperature 150°C)
  • Switching off in limit positions from position and from torque
  • Adjustable switching off from 50% to 100%
  • Torque blocking in limit positions
  • Torque blocking during the start
  • 7 freely programmable relays R1, R2, RE1 ... RE5 (18 functions) (Not valid for Profibus and Modbus)
  • 2 relays READY (Not valid for Profibus and Modbus)
  • Control by unified signal 0/4 - 20 mA, 4 - 12 mA, 12 - 20 mA, or 0/2 - 10 V (Not valid for Profibus and Modbus)
  • Control by permanent voltage (+24 V DC) - OPEN, CLOSE
  • Impulse control (inching duty) (+24 V DC) - OPEN, STOP, CLOSE
  • Timing mode / regime of operation
  • Safety function ESD (failure reaction)
  • Electronic position transmitter 4 to 20 mA passive (not for DMS3 in 2P version) (Not valid for Profibus and Modbus)
  • Auxiliary voltage output 24 V DC, max. 40 mA for supply of the control inputs and transmitter
  • Output of failure messages
  • Space heater operated by control unit
  • LED position indicator
  • Communication interface RS 232
  • Programme for parameterization setting a PC
  • Mechanical connection according to ISO 5210, flange size F14, shape B1, B2, B3, C, D
  • Mechanical connection according to ISO 5210, flange size F16, shape B2, B3, C, D
  • Manual control
  • Enclosure protection IP 67

Additional equipment

  • Supply voltage 220 V AC, 380 V AC
  • Reversing unit for 3-phase supply voltage
  • Communication cable DB-9F/RJ45
  • Mechanical connection according to ISO 5210, flange size F14, shape A
  • Mechanical connection according to ISO 5210, flange size F16, shape A
  • Mechanical connection acording to ГOCT P 55510, shape B, V
  • Local control unit for actuators with DMS 3 system
  • Version with control board PROFIBUS DP V0/V1
  • Version with control board MODBUS RTU

Similar products

Wedge, lid or yoke sliders

Light: DN 50, DN 600 Work pressure: PN 16 Operating temperature: 70 °C Connection parameters: PN EN 1092-2, ISO 7005-2 Construction length acc: ANSI B16.1, flange design EN 558, series 15, DIN 3202-1/F5, welding version EN 12 982, series 15, (DIN 3202-1/S8)
Light: DN 50, DN 600 Work pressure: PN 16 Operating temperature: 70 °C

Knife sliders

Light: DN 50, DN 1000 Work pressure: PN 10/16 Operating temperature: 70 °C Connection parameters: PN EN 0192-2, DIN 2501 Materials: Monolith body - ductile iron EN-GJS-400-15 (GGG-40), Wedge – fully rubberized with antibacterial EPDM, NBR, Spindle - corrosion-resistant steel 1.4021 (13% Cr), O - rings - NBR, Spindle nut – forged brass
Light: DN 50, DN 1000 Work pressure: PN 10/16 Operating temperature: 70 °C

Soft-sealing wedge sliders

Light: DN 40, DN 1200 Work pressure: PN 10/16 Operating temperature: 70 °C Connection parameters: EN 0192-2 with flanges type 21, shape B Construction length acc: 15 – according to PN-EN 558+A1, F5 (DIN 3202), 14 – according to PN-EN 558+A1, F4 (DIN 3202)
Light: DN 40, DN 1200 Work pressure: PN 10/16 Operating temperature: 70 °C

Category products

Electric multi-turn actuator SOR 2PA

Type number: 067 Industry use: Energy, Water, Industry Enclosure: IP 67, IP 68 Trip torque: 12 to 100 Nm Rebuild speed: 10 to 40 min−1
Type number: 067 Industry use: Energy, Water, Industry Enclosure: IP 67, IP 68

Electric multi-turn actuator UMR 1PA

Type number: 181 Industry use: Energy, Water, Industry Enclosure: IP 66, IP 68 Trip torque: 8 to 64 Nm Rebuild speed: 10 to 80 min−1
Type number: 181 Industry use: Energy, Water, Industry Enclosure: IP 66, IP 68

Electric multi-turn actuator UMR 2PA

Type number: 182 Industry use: Energy, Water, Industry Enclosure: IP 66, IP 68 Trip torque: 30 to 100 Nm Rebuild speed: 10 to 40 min−1
Type number: 182 Industry use: Energy, Water, Industry Enclosure: IP 66, IP 68

Electric multi-turn actuator MOR 3PA

Type number: 094 Industry use: Energy, Water, Industry Enclosure: IP 67 Trip torque: 45 to 250 Nm Rebuild speed: 10 to 95 min−1
Type number: 094 Industry use: Energy, Water, Industry Enclosure: IP 67

Electric multi-turn actuator MOR 3.4PA

Type number: 106 Industry use: Energy, Water, Industry Enclosure: IP 67 Trip torque: 150 to 350 Nm Rebuild speed: 10 to 80 min−1
Type number: 106 Industry use: Energy, Water, Industry Enclosure: IP 67

Electric multi-turn actuator MOR 5PA

Type number: 158 Industry use: Energy, Water, Industry Enclosure: IP 67 Trip torque: 500 to 1000 Nm Rebuild speed: 15 to 100 min−1
Type number: 158 Industry use: Energy, Water, Industry Enclosure: IP 67

Electric multi-turn actuator MOR 4PA

Type number: 161 Industry use: Energy, Water, Industry Enclosure: IP 67 Trip torque: 200 to 500 Nm Rebuild speed: 16 to 180 min−1
Type number: 161 Industry use: Energy, Water, Industry Enclosure: IP 67

Electric multi-turn actuator MOR 3.5PA

Type number: 096 Enclosure: IP 67 Trip torque: 140 to 550 Nm Rebuild speed: 25 to 40 min−1 Scope of work. of revolutions: 1 to 400
Type number: 096 Enclosure: IP 67 Trip torque: 140 to 550 Nm

An important fact of reliable operation is not only the correct design of fittings and servo drives, but also their subsequent care. With regular inspections and planned maintenance, you will prevent malfunctions and thus increase the reliability of the operation and extend its service life. For this purpose, the company REGADA also offers you comprehensive care of servo drives in your operation or just a selection from some of the listed services:

  1. Supervision during the first start-up of actuators in operation
  2. Connection and testing of actuators
  3. Connections and start-up of Rematic actuators - instruction
  4. Attaching the actuators to the valves and starting them
  5. Maintenance of actuators and periodic inspections
  6. Post-warranty repairs at the customer
  7. Post-warranty repair offer in Regada
  8. Training of service personnel
  9. Spare parts
download-icon Download files